Module 2 cổng Ethernet Modbus TCP & MQTT 10 kênh Power Relay ICP DAS ET-2261 CR
Features
Introduction
Providing various digital I/O functions, the ET-2261 module is an Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industry and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2261 module perfect integration with the HMI, SCADA, PLC, and other software systems.
The ET-2261 supports 10 Form A electromechanical relays output channels. With 2 Ethernet ports, the ET-2261 allows daisy chain connection which permits flexibility in locating devices, eases installation, and lowers infrastructure costs. It features 8 kV ESD protection, 4 kV EFT protection, 3 kV surge, and 3000 VDC I/O isolation to enhance noise protection capabilities in industrial environments.
The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2261 module can poll the status of remote DI channels via the Modbus TCP protocol and write data to local DO channels.
It is equipped with a removable terminal block connector for easy and robust wiring in industrial situations and features a powerful 32-bit ARM MCU to handle efficient network trafficking.
ET-2261 module supports MQTT protocol and can act as a message publisher and subscriber. After connecting to the server MQTT Broker, the I/O status of the module can be published in the form of a topic, and can also receive messages from the same subscription topics. In communication, when the ET-2261 module is disconnected from the broker, the module has a reconnection mechanism that can automatically reconnect with the broker. In addition, there is a Keep-Alive Interval mechanism to ensure that the connection with the Broker is always maintained.
The ET-2261 supports the standard SNMP V2c specification. Through this specification, ET-2200 can transmit module information and I/O information to SNMP network management equipment or software (SNMP Network Management Software) to help administrators monitor the status of ET-2200 in real time. If the Trap function is enabled, when the module I/O status changes or reboots, it can send a message to the manager to keep track of the channel status at any time.
Applications
Factory, Building and Home Automation Remote Maintenance.
Specifications
Software | |
---|---|
Built-in Web Server | Yes |
CPU Module | |
---|---|
CPU | 32-bit ARM |
Watchdog Timer | Module, Communication (Programmable) |
Isolation | |
---|---|
2-way Isolation | Ethernet: 1500 VDC I/O: 3000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±8 kV Contact for Each Terminal ±16 kV Air for Random Point |
Surge (IEC 61000-4-5) | ±3 kV for Power Line |
LED Indicators | |
---|---|
Status | Run, Ethernet, I/O |
Relay Output | |
---|---|
Channels | 10 |
Type | Power Relay, Form A (SPST N.O.) |
Contact Rating | 5 A @ 250 VAC/24 VDC (Resistive Load) |
Operate Time | 10 ms (max.) |
Release Time | 5 ms (max.) |
Electrical Endurance | 10^5 ops |
Mechanical Endurance | 2 x 10^7 ops |
Power on Value | Programmable |
Safe Value | Programmable |
Ethernet | |
---|---|
Ports | 2 x RJ-45, 10/100 Base-TX, Switch Ports |
LAN bypass | Yes |
Security | Password and IP Filter |
Protocol | Modbus TCP, Modbus UDP, MQTT, and SNMP V2c |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Consumption | 3.8 W (max.) |
Powered from Terminal Block | +10 to +30 VDC |
Mechanical | |
---|---|
Casing | Plastic |
Dimensions (mm) | 33 x 126 x 108 (W x L x H) |
Installation | DIN-Rail mounting |
Environment | |
---|---|
Operating Temperature | -25 to +75 °C |
Storage Temperature | -40 to +80 °C |
Humidity | 10 to 90% RH, Non-condensing |
Download
Ordering Information
ET-2261 CR | Ethernet I/O Module with 2-port Ethernet Switch and 10-ch Power Relay (RoHS) |