Module RS-485 Modbus RTU 16 kênh đầu vào tương tự (Dòng điện, điện áp, cặp nhiệt) ICP DAS M-7018-16-G CR
Tính năng
• 16-channel Differential Analog Input
• Current, Voltage or Thermocouple Input
• Adjustable CJC offset
• Open Thermocouple Detection
• Built-in Dual Watchdog
Giới thiệu
The M-7018-16 is an analog input module that includes 16 differential analog input channels. The voltage input range can be from ±15 mV to ±2.5 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 thermocouple can be used for the thermocouple input. Overvoltage protection of up to 30 VDC is provided. The module also features per-channel open wire detection for the thermocouple input types, and provides 4 kV ESD protection as well as 3000 VDC intra-module isolation.
Ứng dụng
Thông số kỹ thuật
CPU Module | |
---|---|
Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 3000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV to Power |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
Surge (IEC 61000-4-5) | ±2 kV for Power Line |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Analog Input | |
---|---|
Channels | 16 Differential |
Type | Voltage Current Thermocouple |
Sensor Type | Thermocouple: J, K, T, E, R, S, B, N, C |
Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor) |
Resolution | 16-bit |
Accuracy | ±0.1% of FSR |
Sampling Rate | 10 Hz (Total) |
Input Impedance | > 400 kΩ |
Common Voltage Protection | 25 VDC |
Overvoltage Protection | ±30 VDC |
Open Wire Detection | Yes |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 to 115200 bps |
Data Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 0.5 W |
Mechanical | |
---|---|
Dimensions (mm) | 120 x 76 x 42 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering information
M-7018-16-G CR | 16-ch Thermocouple Input Module using DCON and Modbus Protocols (Gray Cover) (RoHS) |