Tổng tiền thanh toán:
-
Sản phẩm đã được thêm vào giỏ hàng
Số lượng:
Tổng tiền:
8-ch Isolated (Wet) DI Module with LED Display
Module RS-485 Modbus RTU 8 kênh đầu vào số DI ICP DAS M-7052D-G CR
Features
Introduction
M-7052/M-7052D provides 6 fully independent channels that can be used individually for devices with different voltage levels and 2 common ground channels for digital inputs. The differential inputs feature channel-to-channel isolation. Either sink-type or source-type input can be selected via wire connections, and all channels are also able to be used as 16-bit counters. M-7052D has 8 LED indicators for channel status monitoring. M-7052(D) supports Modbus RTU and DCON protocols, which can be configured via software. 4 kV ESD protection and 5000 Vrms intra-module isolation are standard, and all hardware specifications are the same as I-7052(D).
Applications
• All Types of ON/OFF Control
• Building Automation
• Industrial Automation
• Industrial Machinery
• Food and Beverage Systems
• Semiconductor Fabrication
• Control Systems
Specifications
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Display | |
---|---|
Type | I/O LED Indicator |
Isolation | |
---|---|
Intra-module Isolation | 5000 Vrms |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
LED Indicators | |
---|---|
Status | 1 x Power and Communication 8 x Digital Input |
Digital Input/Counter | |
---|---|
Channels | 8 |
Type | Wet Contact |
Sink/Source (NPN/PNP) | Sink/Source |
ON Voltage Level | +4 ~ +30 VDC |
OFF Voltage Level | +1 VDC Max. |
Max. Counts | 65535 (16-bit) |
Frequency | 100 Hz |
Min. Pulse Width | 5 ms |
Input Impedance | 3 kΩ |
Overvoltage Protection | ±35 VDC |
Channel-to-Channel Isolation | ±2 kV for differential only |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 0.6 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering Information
M-7052D-G CR | 8-ch Isolated (Wet) DI Module with LED Display, using DCON and Modbus Protocols (Gray Cover) (RoHS) |
Số lượng: