Module 1 kênh đầu ra tương tự 12 bit kết nối RS-485 Modbus RTU & DCON ICP DAS M-7021A
Introduction
The I-7021 is a 12/16-bit, 1-channel Analog Output module that is designed for both voltage and current output. The I-7021 features 3000 VDC intra-module isolation, and the power source for the current output can be selected as either internal or external via a jumper. Options are also provided to allow power-on and safe values to be set. The M-7021A supports both the Modbus RTU and the DCON protocols which can be configured via software, and all hardware specifications are the same as the I-7021.
Features
Current or Voltage Output
High Resolution: 12-bit
Software Selectable Current or Voltage Output
Open Wire Detection for Current Output
Readback Voltage or Current
Configurable Power-on Value
Configurable Safe Value
3000 VDC Intra-module Isolation
Programmable Output Slope
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
I/O Specification
Models |
I-7021 |
I-7021P |
M-7021A |
|
Analog Output |
||||
Channels |
1 |
|||
Wiring |
Unipolar |
|||
Range |
Voltage |
0 ~ +10 V, |
0 ~ +5 V, |
|
Current |
0 ~ +20 mA, +4 ~ +20 mA |
|||
Resolution |
12-bit |
16-bit |
12-bit |
|
Accuracy |
0.1% |
0.02% |
0.1% |
|
Readback Accuracy |
±0.5% of FSR |
|||
DA Output Response Time |
10 ms |
|||
Programmable Output Slope |
Voltage |
0.0625 ~ 1024.0 V/Second |
||
Current |
0.125 ~ 2048 mA/Second |
|||
Current Load Resistance |
Internal Power: 500 Ω |
|||
External Power: 1050 Ω |
||||
Open Wire Detection (for current only) |
Yes |
|||
Channel-to-Channel Isolation |
- |
|||
Short Circuit Protection |
Yes |
|||
Power-on Value |
Yes |
|||
Safe Value |
Yes |
System Specification
Models |
I-7021 |
I-7021P |
M-7021A |
Communication |
|||
Interface |
RS-485 |
||
RS-485 Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
||
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
(N, 8, 1) |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
||
Protocol |
DCON |
Modbus RTU, DCON |
|
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
||
LED Indicator/Display |
|||
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
||
I/O LED Indicator |
- |
||
7-Segment LED Display |
- |
||
Isolation |
|||
Intra-Module Isolation, |
3000 VDC |
||
EMS Protection |
|||
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
||
EFT (IEC 61000-4-4) |
±4 kV to Power Line |
||
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
||
Power |
|||
Reverse Polarity Protection |
Yes |
||
Input Range |
+10 ~ +30 VDC |
||
Consumption |
1.8 W |
||
Mechanical |
|||
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
||
Installation |
DIN-Rail or Wall Mounting |
||
Environment |
|||
Operating Temperature |
-25 to +75°C |
||
Storage Temperature |
-40 to +85°C |
||
Humidity |
10 to 95% RH, Non-condensing |
Download
Odering information
I-7021 CR |
1-channel 12-bit Analog Output Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7021-G CR |
1-channel 12-bit Analog Output Module using the DCON Protocol (Gray Cover) (RoHS) |
I-7021P CR |
1-channel 16-bit Analog Output Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7021P-G CR |
1-channel 16-bit Analog Output Module using the DCON Protocol (Gray Cover) (RoHS) |
M-7021A |
1-channel 12-bit Analog Output Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |