Module 8 kênh đầu vào số cách ly AC/DC kết nối RS-485 DCON & Modbus RTU ICP DAS M-7058D CR
Features
AC/DC Digital Input
8 Differential Input Channels
All Channels Can be used as 16-bit Counters
Channel-to-Channel Isolation
±4 kV ESD Protection
3750 VDC Isolation Voltage
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
Introduction
The I-7058/I-7059 module offers 8 differential channels for AC/DC Digital Input, each of which features channel-to-channel Photocoupleisolation. All DI channels are also able to be used as 16-bit counters. The I-7058D/I-7059D module has 8 LED indicators fthat can be used to monitor the status of the DI channels. ESD protection of ±4 kV and 3750 VDC intra-module isolation are standard. M-7058D/M-7059D module has the same hardware specifi cations as the I-7058/I-7059 module, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.
I/O Specification
Models |
I-7058 |
I-7058D |
I-7059 |
I-7059D |
|
M-7058 |
M-7058D |
M-7059 |
M-7059D |
||
Digital Input/Counter |
|||||
Channels |
8 |
||||
Type |
Dry Contact |
- |
|||
Wet Contact |
Sink/Source |
||||
Wet Contact |
On Voltage Level |
80 ~ 250 VAC |
10 ~ 80 VAC |
||
80 ~ 250 VDC |
15 ~ 80 VDC |
||||
OFF Voltage Level |
30 VAC/VDC Max. |
3 VAC/VDC Max. |
|||
Counters |
Max. Count |
65535 (16-bit) |
|||
Max. Input |
100 Hz |
||||
Min. Pulse Width |
5 ms |
||||
Input Impedance |
68 kΩ |
10 kΩ |
|||
Channel-to-Channel Isolation |
Yes, ±2 kV |
||||
Overvoltage Protection |
300 VAC/VDC Max. |
120 VAC/VDC Max. |
System Specification
Models |
I-7058 |
I-7058D |
I-7059 |
I-7059D |
M-7058 |
M-7058D |
M-7059 |
M-7059D |
|
Communication |
||||
Interface |
RS-485 |
|||
Bias Resistor |
Yes |
|||
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
|||
Baud Rate |
1200 to 115200 bps |
|||
Protocol |
DCON (for the I-7058/I-7059 series) |
|||
Modbus RTU, DCON (for the M-7058/M-7059 series) |
||||
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
|||
LED Indicator/Display |
||||
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
|||
I/O LED Indicator |
- |
Yes, 8 LEDs as Digital Input Indicators |
- |
Yes, 8 LEDs as Digital Input Indicators |
7-Segment LED Display |
- |
|||
Isolation |
||||
Intra-Module Isolation, Field-to-Logic |
3750 VDC |
|||
EMS Protection |
||||
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
|||
±8 kV Air for Random Point |
||||
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
|||
Surge (IEC 61000-4-5) |
- |
|||
Power |
||||
Reverse Polarity Protection |
Yes |
|||
Input Range |
+10 ~ +30 VDC |
|||
Consumption |
0.3 W |
1 W |
0.3 W |
1 W |
Mechanical |
||||
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
|||
Installation |
DIN-Rail or Wall Mounting |
|||
Environment |
||||
Operating Temperature |
-25 to +75°C |
|||
Storage Temperature |
-40 to +85°C |
|||
Humidity |
10 to 95% RH, Non-condensing |
Download
Odering information
I-7058 CR |
8-channel Isolated AC/DC Digital Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7058 CR |
I-7058 with LED Display (Blue Cover) (RoHS) |
I-7058D-G CR |
I-7058 with LED Display (Gray Cover) (RoHS) |
M-7058-G CR |
8-channel Isolated AC/DC Digital Input Module using the DCON and Modbus Protocol (Gray Cover) (RoHS) |
M-7058D-G CR |
M-7058 with LED Display (Gray Cover) (RoHS) |
I-7059 CR |
8-channel Isolated AC/DC Digital Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7059-G CR |
8-channel Isolated AC/DC Digital Input Module using the DCON Protocol (Gray Cover) (RoHS) |
I-7059D CR |
I-7059 with LED Display (Blue Cover) (RoHS) |
I-7059D-G CR |
I-7059 with LED Display (Gray Cover) (RoHS) |
M-7059-G CR |
8-channel Isolated AC/DC Digital Input Module using the DCON and Modbus Protocol (Gray Cover) (RoHS) |
M-7059D-G CR |
M-7059 with LED Display (Gray Cover) (RoHS) |