Module RS-485 Modbus RTU 8 kênh đầu ra Relay ICP DAS M-7064-G CR
Features
Introduction
M-7064/M-7064D provides 8 Form A signal relay output channels. M-7064D includes 8 LED indicators for channel status monitoring. M-7064(D) supports Modbus RTU and DCON protocols, which can be configured via software. There are also options for configuring power-on and safe values. 8 kV ESD, 4 kV EFT and 3 kV surge protection are also provided to enhance noise protection capabilities in industrial environments, making M-7064(D) an ideal solution for small signal-switching applications.
Applications
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Specifications
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 2000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±8 kV Contact for Each Terminal ±16 kV Air for Random Point |
Surge (IEC 61000-4-5) | ±3 kV for Power Line |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Relay Output | |
---|---|
Channels | 8 (Form A) |
Type | Signal Relay |
Contact Material | Silver Nickel, Gold-covered |
Contact Rating | Form A: 2 A @ 30 VDC 0.24 A @ 220 VDC 0.25 A @ 250 VAC |
Operate Time | 3 ms (typical) |
Release Time | 4 ms (typical) |
Electrical Endurance | 2 x 10^5 ops. |
Mechanical Endurance | 1 x 10^8 ops. |
Surge Strength | 2000 VDC |
Power on Value | Programmable |
Safe Value | Programmable |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 1.5 W (Max.) |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering Information
M-7064-G CR | 8-ch Signal Relay Module using DCON and Modbus Protocols (Gray Cover) (RoHS) |