Bộ đổi nguồn Din-Rail 220VAC/24 VDC 10A, 240W ICP DAS SDR-240-24 CR
Feature
Introduction
Application
Specifications
Safety | |
---|---|
Standard | UL508, TUV EN60950-1 approved |
EMC | |
---|---|
Standard | Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved |
Input | |
---|---|
Voltage Range | 88 ~ 264 VAC 124 ~ 370 VDC |
Frequency Range | 47 ~ 63Hz |
AC Current (Typ.) | 2.6 A/115 VAC 1.3 A/230 VAC |
Inrush Current (Typ.) | 33A/115 VAC 65A/230 VAC |
Leakage Current | <1 mA/240 VAC |
Output | |
---|---|
Ripple & Noise (Max.) | 100mVp-p |
Voltage Adj. Range | 24 ~ 28 V |
Voltage Tolerance | ±1.0% |
Line Regulation | ±0.5% |
Load Regulation | ±1.0% |
Setup, Rise Time | 1500ms, 60ms/230 VAC 3000ms, 60ms/115 VAC at full load |
Hold Up Time (Typ.) | 20ms/230 VAC 20ms/115 VAC at full load |
DC Voltage | 24 V |
Rated Power | 240 W |
Rated Current | 10 A |
Efficiency | 94% |
Protection | |
---|---|
Over Voltage | 29 ~ 33V Protection type : Shut down o/p voltage with auto-recovery |
Overload | Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery >150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds |
Function | |
---|---|
DC OK Active Signal (Max.) | 60 VDC/0.3A, 30VDC/1A, 30VAC/0.5A resistive load |
Mechanical | |
---|---|
Casing | Metal |
Dimensions (mm) | (40 * 125.2 * 113.5)mm |
Environment | |
---|---|
Over-temperature Protection | 95°C ±5°C (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
Temperature Coefficient | ±0.03%/°C (0 ~ 50°C) |
Operating Temperature | -25 ~ +70°C (Refer to "Derating Curve") |
Storage Temperature | -40 ~ +85°C |
Humidity | 20 ~ 95% RH Non-condensing |
Download
Ordering Information
SDR-240-24 CR | Power Supply, 88~264 VAC to 24 VDC/10 A, 240 W, DIN-rail mounting (RoHS) |