Module RS-485 DCON 1 kênh đầu vào RTD + 2 kênh DO + 1 kênh DI ICP DAS I-7013-G CR
Features
- 1 RTD Input
- Lead Resistance Elimination for 3/4-wire Connection
- Open Wire Detection
- Built-in Dual Watchdog
Introduction
The I-7013(D) and M-7013P(D) is a 1-channel RTD Input module that is used for measuring temperatures via an RTD sensor and supports Pt100, Ni120, and Pt1000 type sensors. The module allows 2/3/4-wire RTD connections and features open wire detection. In addition, the I-7013(D) and M-7013P(D) also includes 3000 VDC intra-module isolation and supports lead resistance elimination for 3/4-wire connections. The M-7013P and M-7013PD added support for 1-channel digital input as 50 Hz event counter and 2-channel digital output as high/low alarm. The M-7013P and M-7013PD support both the Modbus RTU and DCON protocols, which can be configured via software.
Applications
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Specifications
CPU Module |
Watchdog Timer |
Module, Communication (Programmable) |
Isolation |
Intra-module Isolation |
3000 VDC |
EMS Protection |
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
ESD (IEC 61000-4-2) |
±2 kV Contact for each Terminal |
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
LED Indicators |
Status |
1 x Power and Communication |
Analog Input |
Channels |
1 |
Type |
RTD |
Sensor Type |
Pt100, Pt1000, Ni120 |
Resistance Measurement |
3.2 kΩ Max. |
Resolution |
16-bit |
Accuracy |
±0.05% of FSR |
Sampling Rate |
10 Hz |
Overvoltage Protection |
±5 VDC |
Open Wire Detection |
Yes |
3-wire RTD Lead Resistance Elimination |
Yes |
COM Ports |
Ports |
1 x RS-485 |
Baud Rate |
1200 ~ 115200 bps |
Data Format |
(N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol |
DCON |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
0.7 W |
Mechanical |
Dimensions (mm) |
123 x 72 x 35 (W x L x H) |
Installation |
DIN-Rail Mounting |
Environment |
Operating Temperature |
-25 ~ +75 °C |
Storage Temperature |
-40 ~ +85 °C |
Humidity |
10 ~ 95% RH, Non-condensing |
Download
Datasheet
Documents
Ordering Information
I-7013-G CR |
1-ch RTD Input Module using DCON Protocol (Gray Cover) (RoHS) |