Tổng tiền thanh toán:
-
Sản phẩm đã được thêm vào giỏ hàng
Số lượng:
Tổng tiền:
8-ch Isolated (Wet) DI Module
Module RS-485 DCON 8 kênh đầu vào số DI ICP DAS I-7052 CR
Features
• Differential Digital Inputs
• Sink- or Source-type Input
• 4 kV ESD Protection
• 5000 Vrms Isolation Voltage
• All Channels Can Be Used As 16-bit Counters
• Dual Watchdog
• Wide Operating Temperature Range: -25 ~ +75°C
Introduction
The I-7052 offers 6 fully independent channels and 2 common ground channels for digital input. The diffential inputs feature channel-to-isolation. In addition, you can choose either sink- or source-type input via wire connections. All channels are able to be used as 16-bit has 8 LED indicators for DI channel status monitoring. 4 kV ESD protection and 5000 Vrms intra-module isolation are standard. The M-7052 has the same hardware specifications as the I-7052, but provides additional support for the Modbus RTU protocol as well as the DCON protocol. The I-7053_FG features a long effective distance measurement for dry contact digital input of up to 500 meters. The I-7053_FG supports source-type input. All 16 channels are also able to be used as 16-bit counters, each of which are non-isolated. The I-7053D_FG has 16 LED indicators for channel status monitoring. The M-7053 has the same hardware specifications as the I-7053_FG, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.
Specification
CPU Module | |
---|---|
Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 5000 Vrms |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Digital Input/Counter | |
---|---|
Channels | 8 |
Type | Wet Contact |
Sink/Source (NPN/PNP) | Sink/Source |
Wet Contact, ON Voltage Level | +4 ~ 30 VDC |
Wet Contact, OFF Voltage Level | +1 VDC Max. |
Max. Counts | 65535 (16-bit) |
Frequency | 100 Hz |
Min. Pulse Width | 5 ms |
Input Impedance | 3 KΩ |
Overvoltage Protection | ±35 VDC |
Channel-to-Channel Isolation | Yes, ±2 kV for differential only |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Protocol | DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 0.2 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering information
I-7052 CR | 8-ch Isolated DI (Wet) Module with DCON Protocol (Blue Cover) (RoHS) |