Module EtherCAT Slave 32 kênh đầu vào số DI ICP DAS EC1-P32 CR
Features
Introduction
The EC1-P32 is an industrial slave I/O module built in 32 digital inputs. It is equipped with the EtherCAT protocol and installed by daisy chain connection that provides a more scalable system with fewer wires. Users can obtain the input and output status not only via the process data but also from its LED indicators. The EC1-P32 has passed and verified by the conformance test tool, therefore eligible EtherCAT Master or configurator can manipulate it simply and implement your various applications easily.
Applications
Specifications
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | Signal: 1 KV Class B; Power: 1 KV Class B |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
Surge (IEC 61000-4-5) | ± 1 kV Class A |
Digital Input | |
---|---|
Channels | 32 |
Type | Wet (Sink & Source )/ Dry (Source) |
ON Voltage Level | Wet Contact: +10 V ~ +24 V Dry Contact: Close to GND |
OFF Voltage Level | Wet Contact :+4 V Max. Dry Contact: Open |
Isolation | 3750 VDC |
EtherCAT | |
---|---|
Node ID | Up to 256 |
Distance Between Stations | Max. 100m (100Base-Tx) |
Data Transfer Medium | Ethernet/EtherCAT cable(min. CAT5), shielded |
Cycle Time | 100 us |
Distributed Clocks | Yes |
Power | |
---|---|
Input Range | +24 VDC |
Consumption | 3 W |
Mechanical | |
---|---|
Casing | Metal with IP40 |
Dimensions (mm) | 20 x 98 x 120 (W x L x D) |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -30 ~ +80 °C |
Humidity | 10 ~ 90% RH, Non-condensing |
Download
Ordering Information
EC1-P32 CR | EtherCAT Slave I/O Module with Isolated 32-channel Digital Inputs (RoHS) |