Cam kết 100% chính hãng
Hoàn tiền 111% nếu hàng giả
Giao hàng nhanh chóng & an toàn
Hàng hóa đầy đủ CO, CQ
Hỗ trợ 24/7
Khuyến mãi đặc biệt !!!
Bộ đổi nguồn Din-Rail MCTT-MDR-40-5 30W, 5VDC, 6A





Features:
|
OUTPUT |
|
|||
|
Model |
MCTT-MDR-40-5 |
MCTT-MDR-40-12 |
MCTT-MDR-40-24 |
MCTT-MDR-40-48 |
|
DC Voltage |
5V |
12V |
24V |
48V |
|
Rated Current |
6A |
3.33A |
1.7A |
0.83A |
|
Current Range |
0~6A |
0~3.33A |
0~1.7A |
0~0.83A |
|
Rated Power |
30W |
40W |
40.8W |
39.8W |
|
Ripple & Noise |
80mVp-p |
120mVp-p |
150mVp-p |
200mVp-p |
|
Voltage Adj. Range |
5~6V |
12~15V |
24~30V |
48~56V |
|
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% |
|
Setup, Rise Time |
500ms,30ms/230VAC; 500ms,30ms/115VAC at full load |
|||
|
Hold Up Time |
50ms/230VAC; 20ms/115VAC at full load |
|||
|
INPUT |
|
|||
|
Voltage Range |
85~264VAC (47~63Hz); 120~370VDC |
|||
|
AC Current |
1.1A/115V; 0.7A/ 230V |
|||
|
Efficiency |
78% |
85% |
88% |
88% |
|
Inrush Current |
Cold start, 30A at 115VAC, 60A at 230VAC |
|||
|
Leakage Current |
<1mA/240VAC |
|||
|
PROTECTION |
|
|||
|
Over Load |
105%~150% |
|||
|
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
||||
|
Over Voltage |
115%~135% |
|||
|
Protection type: Shut down o/p voltage, re-power on to recover |
||||
|
Function |
DC OK Signal |
Relay contact rating (max.): 30V/1A resistive |
|
Environment |
Working Temp. |
-20 ~ +70℃ (Refer to “Derating Curve”) |
|
Working Humidity |
20 ~ 90% RH non-condensing |
|
|
Storage Temp., Humidity |
-40 ~ +85℃, 10 ~ 95% RH |
|
|
Temp. Coefficient |
±0.03%/℃ (0 ~ 50℃) |
|
|
Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
|
|
Safety |
Safety Standards |
UI508, TUV EN60950-1, UL60950-1 approved, NEC class 2 compliant |
|
Withstand Voltage |
I/P-O/P:3KVAC, I/P-FG:2KVAC, 1minute |
|
|
EMC standards |
EN55022 class B, EN61000-3-2,-3, ENV50204, EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 heavy industry level |
|
|
Others |
Dimension |
40*90*100mm (L*W*H) |
|
Weight |
0.26Kg |
|
|
Connection |
I/P: 3 poles, O/P: 6 poles screw DIN terminal |
|
|
Note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time. |
|
Download