Bộ chuyển đổi Strain Gauge sang tương tự ICP DAS SG-3016-G CR
Feature
• Three-way isolation: 1000 Vdc
• Accuracy: ±0.1% of full range
• Easy to configure input/output range
• Three VRs for calibrating accuracy of the input/ output range
• Flexible DIN-rail
Introduction
The SG-3016 is a voltage input to voltage or current output signal conditioning module. It has 1000 Vdc three-way isolation for input, output and power. It also can change the input/output range via internal configuration switches. The SG-3016 has an LED display to show whether the SG-3016 is functioning correctly and has three VRs (Zero, Span, Exci) to calibrate accuracy of the input/output range . The bandwidth of the SG-3016 is typically 600 Hz. It is easy to mount the SG-3016 on a standard DIN rail and operate in environments with wide temperature range.
Application
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Specifications
| Isolation | |
|---|---|
| Three-way Isolation | 1000 VDC |
| LED Indicators | |
|---|---|
| Status | Yes, 1 as Power/Communication Indicator |
| Analog Input | |
|---|---|
| Channels | 1 |
| Type | ±10 mV, ±20 mV, ±30 mV, ±50 mV, ±100 mV |
| Accuracy | ±0.1% of full range |
| Bandwidth | <600 Hz |
| Analog Output | |
|---|---|
| Channels | 1 |
| Range | Voltage: 0 ~ 5 VDC, 0 ~ 10 VDC, ±5 VDC, ±10 VDC Current: 0 ~ 20 mA |
| Current Load Resistance | 0 ~ 500 Ω (Source) |
| Excitation Voltage Output | |
|---|---|
| Channels | 1 |
| Range | 0 ~ +10 VDC |
| Max. Load Current | +20 mA |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.44 W (Voltage Output), 1.74 W (Current Output) |
| Mechanical | |
|---|---|
| Dimensions (mm) | 25 mm x 114 mm x 70 mm (W x L x H) |
| Environment | |
|---|---|
| Operating Temperature | -25 °C ~ 75 °C |
| Storage Temperature | -30 °C ~ 75 °C |
| Humidity | 5 ~ 95%, non-condensing |
Download
Ordering Information
| SG-3016-G CR | Strain Gauge Input Signal Conditioner (RoHS) |