I-87082W-G CR: Module 2 kênh đầu vào bộ đếm/tần số (Counter/Frequency)

Thương hiệu: ICP DAS | Tình trạng: Còn hàng
Liên hệ

I-87082W-G CR 2-ch Counter/Frequency Input Module (RoHS)

Gọi +84 904251826 để được trợ giúp

I-87082W-G CR: Module 2 kênh đầu vào bộ đếm/tần số (Counter/Frequency)

Features

• 2-channel Counter/Frequency Input
• 32-bit Counter
• Isolated or Non-isolated Input
• Programmable Alarm Output
• Programmable Digital Filter
• Programmable Threshold Voltage Level
• Maximum Frequency of up to 100 kHz
• Dual Watchdog
• Wide Operating Temperature Range: -25 to +75°C

Introduction

The I-87082W offers 2 high speed counter or frequency input channels and 2 digital output channels. Two types of digital input are provided, one for isolated input, and the other is for nonisolated input. The isolated input provides 3750 Vrms isolation voltage and the non-isolated input provides programmable threshold voltage level. The built-in digital filter is valid for both non-isolated and isolated input and can filter out noise where the high/low pulse width is smaller than the minimum high/low width of the digital filter. The maximum count is up to 32-bit and the maximum frequency is up to 100 kHz. The module also provides programmable alarm output with non-isolated open collectors.

Specification

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)

 

Isolation
Intra-module Isolation 3750 Vrms

 

EMS Protection
ESD (IEC 61000-4-2) ± 4 kV Contact for Each Terminal
±8 kV Air for Random Point

 

LED Indicators
Status 1 x Power and Communication
8 x I/O

 

Digital Output
Channels 2
Sink/Source (NPN/PNP) Sink, Open Collector
Load Voltage +5 VDC ~ +30 VDC
Max. Load Current 30 mA

 

Counter/Frequency/Encoder Input
Channels 2
Type Counter or Frequency
Counter/Encoder Bits 32-bits (4,294,967,295)
ON Voltage Level Sensor Type:
+3.5 VDC ~ +30 VDC

Non-isolated:
0 ~ +5 VDC (Default > 2.4 VDC)
0 ~ +5 VDC (Default < 0.8 VDC)
OFF Voltage Level Sensor Type:
+1 VDC Max.

Non-isolated:
0 ~ +5 VDC (Default > 2.4 VDC)
Max. Counter/Frequency 100 kHz
Frequency Accuracy 1 Hz or 10 Hz (software selectable)
Programmable Alarm Mode Mode 0:
High Alarm Comparator on Counter 0 and Counter 1

Mode 1:
Two Steps High Alarm Comparator on Counter 1
Digital Filter 2 ~ 65000 μs
Counter Mode Up

 

COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format N, 8, 1
Protocol DCON

 

Power
Consumption 0.5 W Max.

 

Mechanical
Dimensions (mm) 30 x 102 x 115 (W x L x H)

 

Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing

Download

Data sheet

Documents

Ordering information

I-87082W-G     CR  2-ch Counter/Frequency Input Module (RoHS)

Sản phẩm đã được thêm vào giỏ hàng

Số lượng:

Tổng tiền:

Sản phẩm đã được thêm vào giỏ hàng

Phí vận chuyển: Tính khi thanh toán

Tổng tiền thanh toán: