6-ch RTD Input Module with 3-wire Lead Resistance Elimination
Module RS-485 Modbus RTU 6 kênh đầu vào RTD ICP DAS M-7015P-G CR
Features
• 6-channel RTD Input
• 3-wire RTD Input with Lead Resistance Elimination
• High Resolution: 16-bit
• Individual Channel Configuration
• Open Wire Detection
• 4 kV ESD Protection
• 4 kV EFT Protection
• 3000 VDC Intra-module Isolation
• Dual Watchdog
• Wide Operating Temperature Range: -25 to +75°C
Introduction
The I-7015 is a series of 6-channel RTD input modules that are used for measuring temperatures using RTD sensors and each channel can be connected to a different type of sensor. The I-7015P/M-7015P is specifically designed for long-distance RTD measurement, and features automatic compensation for three-wire RTD, meaning that accurate measurements can be obtained regardless of the length of the wires. The I-7015 series is fully RoHS-compliant and features 4 kV ESD protection as well as 3000 VDC intra-module isolation. The M-7015/M-7015P supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7015/I-7015P.
Specification
CPU Module | |
---|---|
Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 3000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Analog Input | |
---|---|
Channels | 6 |
Type | RTD |
Sensor Type | Pt100, Pt1000, Ni120, Cu50, Cu100, Cu1000 |
Resistance Measurement | 3.2 kΩ Max. |
Resolution | 16-bit |
Accuracy | ±0.05% of FSR |
Sampling Rate | 12 Hz (Total) |
Overvoltage Protection | 120 VDC |
Individual Channel Configuration | Yes |
Open Wire Detection | Yes |
3-wire RTD Lead Resistance Elimination | Yes |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 1.2 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering information
M-7015P-G CR | 6-ch RTD Input Module with 3-wire Lead Resistance Elimination using DCON and Modbus Protocols (Gray Cover) (RoHS) |
Số lượng: