-
-
-
Tổng tiền thanh toán:
-
Sản phẩm đã được thêm vào giỏ hàng
Số lượng:
Tổng tiền:
Modbus Data Concentrator with Ethernet, RS-485 Serial Ports and Data Logger
Bộ dữ liệu tập trung Modbus + Data Logger 5xRS-485 + 1xEthernet ICP DAS MDCL-705i CR
Feature
Introduction
The Modbus Data Concentrator is the ideal product for IIoT system integrators. The MDCL-705i is used to collect and store data from multiple Modbus slave devices over the serial communication interface and make the data available to back-end management system via Ethernet communication. In this way, conventional devices can be attached to a modern control system and through the Modbus TCP protocol easily communicates with most SCADA / HMI systems and PLCs. Thus the management system can poll the MDCL-705i for the data from several Modbus devices at once; making the process much more efficient.
The MDCL-705i can help you build a cost-effective data acquisition solution for reading real-time data from meters, sensors and more. The ability to integrate with SCADA systems and other industrial devices, and the reliable real-time data collection in combination with the data logger makes MDCL-705i one of the most cost-effective products of IIoT.
Modbus Data Concentrator
The MDCL-705i collects data using the Modbus RTU protocol to poll the data out of the device. For each data you want to retrieve, just define the Modbus RTU commands in a CSV file and import it via the web interface. The MDCL-705i can perform up to 250 polling definitions. Its internal shared memory has four tables (Coils, Discrete Input, Input Registers and Holding Registers) to store the polled data. Each table can store up to 9600 registers. It allows up to 8 simultaneous Modbus TCP connections to get the polled data at one time.
Stand-alone data logging capability
The MDCL-705i uses a periodic method to record user-specified Modbus register data. Each data can contain up to 120 parameters. The data records will be stored in the built-in microSD memory card in CSV file format and can be downloaded to the computer through the built-in web interface. Data viewing and data analysis can be performed using Microsoft Excel software or a plain text editor.
Application
Specifications
Data Logger | |
---|---|
Data Type | Boolean, 16-bit Integer, 32-bit Integer and 32-bit Floating |
Max. Recording Period per File | 1 hr, 2 hr, 6 hr, 12 hr, 24 hr |
File Manager Interface | Built-in web server |
Storage Media | microSD Card (Up to 32 GB) |
File Format | CSV |
Time Interval | 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min, 1 hr, 6 hr |
Max. Records | 120 parameters per record |
Display | |
---|---|
Type | 5-Digit 7 Segment LED Display (display system information) |
LED Indicators | |
---|---|
Status | 1 x System, to (display heartbeat) |
COM Ports | |
---|---|
Ports | 2 x 2-wire RS-485 (non-isolated) 3 x 2-wire RS-485 (2.5 kV isolation protection) |
Baud Rate | 1200, 2400, 4800, 9600, 14400, 19200, 38400, 57600, 115200 bps |
Data Format | N81, E81, O81, N82, E82, O82 |
Protocol | Modbus RTU Master/Modbus RTU Slave |
Polling Definition | 250 definitions for all RS-485 ports |
Shared Memory | 9600 registers for each of AI, AO, DI and DO data |
Max. Connection | 32 slaves for each RS-485 port |
Ethernet | |
---|---|
Ports | 10/100 Base-TX |
Protocol | Modbus/TCP slave, HTTP |
Socket Connections | 8 Modbus/TCP |
Power | |
---|---|
Input Range | +10 ~ +48 VDC |
Consumption | 2 W |
Mechanical | |
---|---|
Casing | Metal |
Dimensions (mm) | 97 x 120 x 42 (W x L x H) |
Installation | DIN-Rail or Wall Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -30 ~ +80 °C |
Humidity | 10 ~ 90 % RH, Non-condensing |
Download
Ordering Information
MDCL-705i CR | Modbus Data Concentrator with Ethernet, RS-485 Serial Ports and Data Logger (RoHS) |
Số lượng:
Tổng tiền: