Module RS-485 Modbus RTU 3 kênh DI + 3 kênh Relay ICP DAS tM-PD3R3 CR
Features
Introduction
The tM-PD3R3 provides 3 channels for digital input and 3 channels for relay output, each of which features photocoupler isolation. All output channels are Form A-type relays, while the input is based on the sink- or source-type using a wire connection. All input channels can be used as 16-bit counters. There are options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
Applications
• All Kinds of On/Off Control
• Industrial Automation
• Industrial Machinery
• Building Automation
• Food and Beverage Systems
• Semiconductor Fabrication
• Control Systems
Specifications
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 3750 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Digital Input/Counter | |
---|---|
Channels | 3 |
Type | Dry Contact |
Sink/Source (NPN/PNP) | Source |
ON Voltage Level | Close to GND |
OFF Voltage Level | Open |
Max. Counts | 65535 (16-bit) |
Frequency | 100 Hz |
Min. Pulse Width | 5 ms |
Input Impedance | - |
Overvoltage Protection | - |
Relay Output | |
---|---|
Channels | 3 |
Type | Power Relay, Form A (SPST N.O.) |
Operate Time | 6 ms |
Release Time | 3 ms |
Electrical Endurance | VDE: 5 A @250 VAC 30,000 ops (10 ops/minute) at 75°C 5 A @30 VDC 70,000 ops (10 ops/minute) at 75°C UL: 5 A @250 VAC/30 VDC 6,000 ops 3 A @250 VAC/30 VDC 100,000 ops 5 A @30 VDC 70,000 ops (10 ops/minute) at 75°C |
Mechanical Endurance | 20,000,000 ops at no load (300 ops/minute) |
Surge Strength | 250 VAC or 30 VDC |
Power on Value | Programmable |
Safe Value | Programmable |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
Protocol | DCON, Modbus RTU, Modbus ASCII |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Consumption | 0.9 W Max. |
Powered from Terminal Block | 10 ~ 30 VDC |
Mechanical | |
---|---|
Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -30 ~ +75 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering Information
tM-PD3R3 CR | 3-channel Isolation DI (Dry) and 3-channel Power Relay Module (RoHS) |