Module RS-485 DCON 1 kênh đầu vào tương tự AI+ 2 kênh DO + 1 kênh DI ICP DAS I-7012F CR
Features
• Current or Voltage Input
• High Resolution: 16-bit
• High/Low Alarm (Digital Output)
• 50 Hz Event Counter (Digital Input)
• 100 Hz High Sampling Rate
• 3000 VDC Intra-module Isolation
• Dual Watchdog
• Wide Operating Temperature Range: -25 to +75°C
Introduction
The I-7012 is an Analog Input module that is designed for both voltage and current input types. In addition, the module provides 1 Digital Input channel as a 50 Hz event counter and 2 Digital Output channels that can be used as a high/low alarm. The I-7012 also features 3000 VDC intra-module isolation. The I-7012F is an Analog Input module that is designed for both voltage and current input types. The sampling rate for the I-7012F is adjustable and can be switched between fast mode and normal mode depending on your requirements. In addition, the module provides 1 Digital Input channel as a 50 Hz event counter and 2 Digital Output channels that can be used as a high/low alarm. The I-7012F also features 3000 VDC intra-module isolation.
Specification
CPU Module | |
---|---|
Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 3000 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV to Power Line |
ESD (IEC 61000-4-2) | ±2 kV Contact for each Terminal |
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Analog Input | |
---|---|
Channels | 1 Differential |
Type | Voltage Current |
Range | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA (requires optional external 125 Ω resistor) |
Resolution | 16-bit |
Accuracy | Normal Mode: 0.05% Fast Mode: 0.25% |
Sampling Rate | Normal Mode: 10 Hz Fast Mode: 100 Hz |
Input Impedance | 20 MΩ |
Common Voltage Protection | ±100 VDC |
Overvoltage Protection | ±120 VDC |
Digital Input/Counter | |
---|---|
Channels | 1 |
Type | Dry Contact |
Sink/Source (NPN/PNP) | Source |
Dry Contact, ON Voltage Level | Close to GND |
Dry Contact, OFF Voltage Level | Open |
Max. Counts | Yes, 50 Hz, 16-bit |
Input Impedance | 3 kΩ |
Overvoltage Protection | ±30 VDC |
Digital Output | |
---|---|
Channels | 2 |
Type | Open Collector |
Sink/Source (NPN/PNP) | Sink |
Load Voltage | +3.5 ~ +30 VDC |
Max. Load Current | 30 mA/Channel |
Power on Value | Yes |
Safe Value | Yes |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | N, 8, 1 |
Protocol | DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 1.3 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Odering information
I-7012F CR | 1-ch AI (Fast Sampling Version) Module using DCON Protocol (16-bit) (Blue Cover) (RoHS) |