Module RS-485 DCON 16 kênh đầu ra số DO ICP DAS I-7045D-NPN-G CR
Features
• Sink-type Digital Output Channels with Overload Protection
• Configurable Power-on Value Settings
• Configurable Safe Value Settings
• Short Circuit Protection
• Overload and Overvoltage Protection
• 3750 VDC Intra-module Isolation
• 4 kV ESD and EFT Protection
• 3 kV Surge Protection for Power Input
• Dual Watchdog
• Wide Operating Temperature Range: -25 ~ +75°C
Introduction
All modules in the 7045 series offer 16 digital output channels, each of which features Photocouple isolation. The I-7045(D)/M-7045(D) supports sourcetype output, while the I-7045(D)-NPN/M-7045(D)-NPN supports sink-type, and both are equipped with short circuit protection. There are options to enable both power-on and safe values, and 16 LED indicators that can be used to monitor the status of the digital output channels. 4 kV ESD protection, 4 kV EFT protection, 3 kV surge protection for power input and 3750 VDC Intra-module isolation are standard. The M-7045(D)/M-7075(D)-NPN has the same hardware specifications as the I-7045(D)/I-7045(D)-NPN, but provides additional support for the Modbus RTU protocol as well as the DCON protocol.
Specification
CPU Module | |
---|---|
Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
Display | |
---|---|
Type | I/O LED Indicator |
Isolation | |
---|---|
Intra-module Isolation | 3750 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for the 16 DO channels and Power, ±2 kV for the RS-485 Port |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
Surge (IEC 61000-4-5) | ±3 kV for Power Line |
LED Indicators | |
---|---|
Status | 1 x Power and Communication 16 x Digital Output |
Digital Output | |
---|---|
Channels | 16 |
Type | Open Collector |
Sink/Source (NPN/PNP) | Sink |
Load Voltage | +3.5 ~ 50 VDC |
Max. Load Current | 700 mA/Channel |
Overvoltage Protection | 60 VDC |
Overload Protection | 1.4 A (with Short-circuit Protection) |
Short-Circuit Protection | Yes |
Power on Value | Yes |
Safe Value | Yes |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 to 115200 bps |
Data Format | N, 8, 1 |
Protocol | DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 1.2 W |
Mechanical | |
---|---|
Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering information
I-7045D-NPN-G CR | 16-ch Isolated DO (Sink, NPN, 3.5~50 VDC) Module with LED Display using DCON Protocol (Gray Cover) (RoHS) |