-
-
-
Tổng tiền thanh toán:
-
Sản phẩm đã được thêm vào giỏ hàng
Số lượng:
Tổng tiền:
1-CH Lighting Control Module with AC Load Current Measurement (1 AC DI + 1 Relay output)
Module điều khiển đèn chiếu sáng ICP DAS LC-101H CR
Feature
Introduction
The LC lighting control module is easy-to-use and requires no specialist skills to install and operate, and no software is needed in order to control the lighting control channels.
The LC-101H is a 1-channel lighting control module with AC load current measurement which provides 1-channel high power relay output and 1-channel AC digital input.
The AC load current measurement is provided in the relay control loop. This function not only allows the user to know the load current value, but also through the measurement of the load current value, it can be used to know the switching state of the relay, whether the load is working normally in the light control loop, or the relay is stuck and cannot be switched.
The input channel can directly control the relay ON and OFF sequence without the host command.
When required, the module can be communicated with the Modbus RTU protocol, and an added benefit is that different addresses can be set for Modbus RTU communication via hardware configuration.
Application
Specifications
Software | |
---|---|
Function | Local and Remote Direct Control Relay ON/OFF and Remote Status Monitoring |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
Surge (IEC 61000-4-5) | ±2 kV for Power |
LED Indicators | |
---|---|
Status | 1 LED as Power Indicator |
Digital Input | |
---|---|
Channels | 1 |
Type | Wet Contact, 90 ~ 240 VAC |
ON Voltage Level | 65 VAC |
OFF Voltage Level | 56 VAC |
Isolation | 3000 VDC |
Input Impedance | 68 KΩ, 2W |
Relay Output | |
---|---|
Channels | 1 |
Type | Power Relay, Form C (SPDT N.O+N.C..) |
Contact Rating | 30 A @ 250 VAC |
AC Load Current Measurement | Yes, 0 ~ 5 A range with 3% of FSR Accuracy. |
Operate Time | 15 ms Max |
Release Time | 22 ms Max. |
Electrical Endurance | 100,000 ops. |
Mechanical Endurance | 10,000,000 ops |
Power on Value | Yes |
Safe Value | Yes |
Application Specification | (1).Incandescent Lamp: 40W/ 220VAC * 5 Sets (2).LED(Electronic ballast): 40W/ 220VAC *8 Sets |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | Hardware Configuration: Fixed 9600 bps Software Configuration: 1200 to 115200 bps |
Data Format | N,8,1/O,8,1/E,8,1/N,8,2 |
Protocol | Modbus RTU/DCON |
Ethernet | |
---|---|
Node Address | 32 to 63 for hardware configuration |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | 10 ~ 30 VDC |
Consumption | 1.9 W Max. |
Mechanical | |
---|---|
Dimensions (mm) | 72 mm x 95 mm x 57 mm |
Installation | DIN-Rail |
Environment | |
---|---|
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -30 ~ +75°C |
Humidity | 10 ~ 95% RH, Non-condensing |
Download
Ordering Information
LC-101H CR | 1-CH Lighting Control Module with AC Load Current Measurement (1 AC DI + 1 Relay output) (RoHS) |
Số lượng:
Tổng tiền: