Module Profibus Slave 8 kênh đầu vào tương tự AI ICP DAS PROFI-5017 CR
Features
• Protocol & Hierarchy : DP-V0 Slave
• Supports Transmission Rate (kbps) : 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
• Transmission Rate Setting : detected automatically
• Address Setting : Address 0~126 set by rotary switches or SSA Telegram
• Indicators : PWR LED, RUN LED, ERR LED
• I/O modules Configuration : Configured by GSD file
• Network Isolation Protection : High Speed iCoupler
• DC Isolation Protection : 3000 VDC on PROFIBUS side
• 4KV ESD Protection : Contact for each terminal
Introduction
The PROFI-5017 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 8-channel isolated analog voltage input with 2500Vrms field to logic isolation. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.
Specifications
CPU Module | |
---|---|
CPU | 80186, 80 MHz or compatible |
EEPROM | 2 KB |
Flash | 512 KB |
SRAM | 512 KB |
Watchdog Timer | Watchdog IC CPU built-in |
LED Indicators | |
---|---|
Status | PWR LED, RUN LED, ERR LED |
Analog Input | |
---|---|
Channels | 8 channel differential voltage input, Isolation Voltage:2500Vrms |
Range | +/- 10V, +/- 5V, +/- 2.5V, +/-1.25V |
Accuracy | +/- 0.1 of FSR |
PROFIBUS | |
---|---|
Controller | Siemens SPC3 |
Transceiver | ADI ADM2486 |
Baud Rate | 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M |
Isolation | 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic |
Protocol | DP-V0 |
Power | |
---|---|
Consumption | 3 W |
Mechanical | |
---|---|
Dimensions (mm) | 91 x 128 x 52 (W x L x H) |
Installation | DIN-Rail |
Environmental | |
---|---|
Operating Temperature | -25 ~ +75℃ |
Storage Temperature | -30 ~ +80 ℃ |
Humidity | 10 ~ 90% RH, Non-condensing |
Download
Ordering information
PROFI-5017 CR | PROFIBUS Remote I/O Module (8-channel Isolated Analog Voltage Input) (RoHS) |